Heat pump sizing Calculator: how many kW you need and what your heating costs compared with gas, electricity, pellets or firewood

An undersized heat pump runs non-stop and still does not heat the house. An oversized one starts and stops often, uses more electricity and wears out faster. The calculator below asks the same questions the technician asks on site: floor area, insulation, windows, heating system and hot water. You get the power in kW, the right Chofu model and what your heating costs per year compared with gas, pellets, firewood or direct electric heating.

Tell us about your house

These are the questions the technician asks on site. The answer updates as you fill them in.

House

m²
m

Heating system

What do you want from the pump?

Heating type
People
m

Insulation

Wall insulation
cm
Loft insulation
cm
Windows

Send the sizing to NEDAVI

We check the figure with a technician, then you get an itemised quote: heat pump, cylinder, installation, delivery. No obligation.

We'll reply within one working day. Your details go only to NEDAVI COM SRL and we don't pass them on.

How many kW you need: table by floor area and insulation

The table uses the same formula as the calculator above: 55 W/m² for a well insulated house, 75 W/m² for average insulation and 100 W/m² for a poorly insulated one, multiplied by the heated floor area, corrected for the ceiling height (2.6 m) and the shape of the house (ground floor plus first floor), plus 0.8 kW for the hot water of 4 people. The proposed model is for underfloor heating.

Heat demand and the proposed Chofu pump, by floor area and insulation
Heated floor area well insulated (55 W/m²)average insulation (75 W/m²)poorly insulated (100 W/m²)
80 m² 5.2 kW
Chofu 6 kW R32
6.8 kW
Chofu 8 kW R290 Standard
8.8 kW
Chofu 8 kW R290 Standard
100 m² 6.3 kW
Chofu 6 kW R32
8.3 kW
Chofu 8 kW R290 Standard
10.8 kW
Chofu 10 kW R32
120 m² 7.4 kW
Chofu 8 kW R290 Standard
9.8 kW
Chofu 10 kW R32
12.8 kW
Chofu 12 kW R32
150 m² 9.1 kW
Chofu 10 kW R32
12.1 kW
Chofu 12 kW R32
15.8 kW
Chofu 16 kW R32
180 m² 10.7 kW
Chofu 10 kW R32
14.3 kW
Chofu 16 kW R32
18.8 kW
Chofu 16 kW R32 · below demand, ask for a survey
200 m² 11.8 kW
Chofu 12 kW R32
15.8 kW
Chofu 16 kW R32
20.8 kW
Chofu 16 kW R32 · below demand, ask for a survey
250 m² 14.6 kW
Chofu 16 kW R32
19.6 kW
Chofu 16 kW R32 · below demand, ask for a survey
25.8 kW
Chofu 16 kW R32 · below demand, ask for a survey
300 m² 17.3 kW
Chofu 16 kW R32
23.3 kW
Chofu 16 kW R32 · below demand, ask for a survey
30.8 kW
Chofu 16 kW R32 · below demand, ask for a survey

A model is proposed if its power covers at least the demand minus 10%, because the design day only comes round a few times each winter, and it is flagged as oversized from 35% above the demand. For radiators or a mixed system, only the models that take the flow temperature to 75 °C qualify, that is the R290 range; the calculator above allows for this when you choose "Radiators" or "Mixed".

Climate zone and design outdoor temperature

The power is sized for the design outdoor temperature of your zone (SR 1907-1), not for the winter average. The yearly cost in the panel above uses 1,980 equivalent hours of running at nominal power, the figure for zone II, and the Chofu SCOP of 4.68 at a 35 °C flow temperature (underfloor heating) or 3.61 at 55 °C (radiators).

Climate zones in Romania and equivalent heating hours
Zone Design temperature Equivalent hours per year Towns
I −12 °C 2,175 h Constanța
II −15 °C 1,977 h Oradea, Arad, București
III −18 °C 1,813 h Cluj, Sibiu, Iași
IV −21 °C – –
V −25 °C – –

How the configurator works out the heat pump power

The power of a heat pump is chosen from how much heat the house loses on the coldest design day, not from the square metres on their own. Two 150 m² houses can need 9 kW or 16 kW, depending on the insulation, the ceiling height and how many people use hot water. The formula behind the calculator is simple and you can check it with a pencil:

kW = heated floor area × W/m² ÷ 1000 × (ceiling height ÷ 2.6 m) × storey factor + people × 0.2 kW

The W/m² value comes from the insulation: 55 W/m² for a well insulated house, 75 W/m² for average insulation and 100 W/m² for a poorly insulated house. We work out the insulation grade from three answers, with different weights: the external walls count for 50% (good from 10 cm of polystyrene or equivalent, average from 5 cm), the loft or roof for 30% (good from 15 cm, average from 8 cm) and the windows for 20% (triple glazing, double glazing or old frames). Mineral wool, rock wool or XPS are converted into equivalent centimetres of polystyrene, so the comparison is fair.

The storey factor is 1.10 for a single storey house, which loses heat through both the floor and the roof over the same area, 1.00 for a ground floor plus first floor and 0.95 when the attic is lived in. A 3 m ceiling instead of 2.6 m adds 15% to the demand, because you are heating more air.

An example: a 150 m² house on two storeys, 2.6 m ceilings, average insulation, four people. 150 × 75 ÷ 1000 = 11.25 kW; the height and the storeys change nothing; hot water adds 4 × 0.2 = 0.8 kW. The demand is 12.05 kW. The calculator proposes the 12 kW model, because it accepts a pump up to 10% below the demand: the design day comes round a few times each winter, and for the rest of the season the pump would run at part load anyway. If the same customer insulates the walls with 10 cm, the house moves to 55 W/m², the demand drops to 9.05 kW and the 10 kW model is enough.

Underfloor heating, radiators or mixed: the flow temperature changes the model

Underfloor heating works with water at 30–35 °C on the flow. Classic radiators need 50–55 °C, and on very cold days even more. The difference shows straight away on the bill: the Chofu SCOP is 4.68 at 35 °C and 3.61 at 55 °C, so the same house uses almost 30% more electricity on radiators than on underfloor heating. That is why the calculator asks what heating system you have.

For radiators or a mixed system, the calculator only proposes models from the R290 range, which take the flow temperature up to 75 °C. The R32 range stops at 60 °C and remains the choice for underfloor heating or fan coils. If you have old steel or cast iron radiators, most of the time they can stay; at the free sizing check we verify whether their radiating surface is enough at 55 °C. More in the articles on a heat pump with your existing radiators and a heat pump with underfloor heating.

Domestic hot water: how much it adds to the power and what cylinder you need

Each person who uses hot water daily adds about 0.2 kW to the power needed. For a family of four, that means 0.8 kW on top of the heating demand. The figure looks small, but in a well insulated 100 m² house it is the difference between 5.5 and 6.3 kW, that is, between a pump that copes and one that is at its limit in January.

The cylinder matters as much as the power. A heat pump heats water more slowly than a gas boiler, so it needs a larger volume and a generous coil: in practice 200 l for two or three people and 300 l from four upwards. If you already have heating and want the pump only for radiators or underfloor heating, choose "Heating only" in the calculator and hot water is left out of the calculation. Which cylinder works, and why not just any will do, in the article on hot water cylinders.

What happens at −15 °C or −20 °C

The power printed on an air-to-water heat pump is measured at 7 °C outside and 35 °C on the flow. The lower the outdoor temperature, the lower the power delivered, while the house asks for more and more. That is why sizing is done for the design outdoor temperature of your county, from the climate zone table above: −15 °C in zone II (Oradea, Arad, Bucharest), −18 °C in zone III (Cluj, Sibiu, Iași), −12 °C on the coast.

Chofu heat pumps are guaranteed to run down to −20 °C, and the data sheet of each model shows the power at −7 °C, so you can see how much of the nominal figure is left when it is properly cold. The calculator here does not yet correct the W/m² value by zone; at the free sizing check we take that step, with the design temperature of your town and the heating system you already have. How the unit works when it is freezing outside, in short, in how an air-to-water heat pump works.

Why oversizing costs more than you think

The temptation is to take "a bigger one, just in case". A heat pump that is too large for the house cannot turn its power down far enough on ordinary winter days, at 0 or 5 °C, when the house may need a third of the design demand. It starts, reaches the temperature in a few minutes, stops, starts again. Every start means electricity used without useful heat and wear on the compressor. The calculator flags a model as oversized when its power exceeds the demand by more than 35%.

The most common mistake is copying the power of the gas boiler. A 24 or 28 kW wall-hung boiler was not chosen for the heat losses of the house but for instant hot water in the shower; the same house usually needs 8–12 kW from a heat pump. The 15 year calculation, with what you gain and what you lose, is in a heat pump instead of the gas boiler. Above 380 m² or above 16 kW, the calculator proposes two or three identical pumps in cascade, the solution for guesthouses and large houses, instead of a single industrial unit.

What your heating costs: gas, electricity, pellets or firewood

The "What your heating costs you per year" panel under the calculator compares the Chofu pump with the heating you have or are considering: condensing gas boiler, pellet boiler, firewood, direct electric heating and other brands of heat pump. You pick the electricity tariff you pay and see the cost per year and per month for the house described above. The method is written under the table too, so you can check it:

heat required = heating power × equivalent hours × gains factor; fuel = heat ÷ seasonal efficiency; cost = fuel × price of one kWh

The heating power is the demand without the hot water share. The equivalent hours are those of zone II, 1977 a year, worked out from Eurostat degree days for 2021–2025. The Chofu pump goes in with a SCOP of 4.68 on underfloor heating or 3.61 on radiators, the gas boiler with an efficiency of 0.92, the pellet boiler and firewood with 0.75, direct electric heating with 1.0. Energy prices are those at the date of publication, 1.35 lei/kWh for electricity on the average tariff and 0.28 lei/kWh for gas, and we update them when the market changes. Consumption over one winter, by model, with real bills, in what a winter with a heat pump costs; how the bill falls with solar panels in heat pumps and solar panels.

How we check the sizing, free of charge

The calculator result is a good estimate, not a quote. When you press "Send sizing", your answers reach us at NEDAVI together with the proposed model. A technician checks them, asks for anything missing (the house plan, photos of the heating system, year of construction, the energy performance certificate if there is one) and replies within one working day with the confirmed power and an itemised quote: pump, cylinder, installation, delivery. For houses with a mixed system, old radiators or more than 250 m², we also do a site survey before the quote. It commits you to nothing.

Frequently asked questions about heat pump sizing

How many kW per square metre does a heat pump need?
Between 55 and 100 W per square metre of heated floor area, that is 0.055–0.1 kW/m²: 55 W/m² for a well insulated house, 75 W/m² for average insulation, 100 W/m² for an old, uninsulated house. To that you add about 0.2 kW per person for hot water and the corrections for high ceilings or a single storey house.
What heat pump power do I need for a 100 m² house?
With four people and hot water: about 6.3 kW if it is well insulated (100 × 55 ÷ 1000 + 0.8), 8.3 kW with average insulation and 10.8 kW if it is poorly insulated. In practice, the 6 kW, 8 kW or 10 kW Chofu model. On radiators, choose from the R290 range.
What power do I need for 150 m²?
About 9 kW for a well insulated house, 12 kW for average insulation and 16 kW for a poorly insulated house, with hot water for four people and 2.6 m ceilings. The calculator proposes 10, 12 or 16 kW. If the house is single storey, add 10%.
And for a 200 m² house?
Roughly 12 kW well insulated and 16 kW with average insulation. An old 200 m² house, at 100 W/m², goes past 20 kW: there the insulation comes first, otherwise we are talking about two pumps in cascade or a site survey before any quote.
How many square metres does a 6, 8, 10, 12 or 16 kW heat pump heat?
In a well insulated house on two storeys: 6 kW up to about 110 m², 8 kW up to 140 m², 10 kW up to 180 m², 12 kW up to 220 m² and 16 kW up to 300 m². With average insulation, the figures drop by almost a third. Each model has its own article: 6 kW, 10 kW, 12 kW and 16 kW three phase.
Can I use the power of the gas boiler I have?
No. Wall-hung boilers of 24–28 kW are sized for instant hot water, not for the heat losses of the house. The same house usually needs 8–12 kW from a heat pump, with a separate cylinder for hot water. If you copy the boiler's power, you get a pump twice too large, which will start and stop often.
Will a heat pump work with my existing radiators?
Most of the time, yes. Chofu R290 models take the water up to 75 °C, a temperature at which classic radiators work normally. The bill will be higher than with underfloor heating, though, because the SCOP at 55 °C is 3.61 against 4.68 at 35 °C. At the sizing check we verify whether the radiator surface is enough at 55 °C; sometimes replacing two or three small radiators is all it takes.
Do I need a backup electric heater?
With a pump sized correctly for the design temperature of your zone, the immersion heater rarely comes on: only on the few days each winter when it is colder than the design value, or when the cylinder runs its anti-legionella cycle. It does not make up for the missing power of a pump that is too small: a kilowatt from the heater costs three or four times more than one from the compressor.
Single phase or three phase?
The 4, 6, 8, 10 and 12 kW models come in 230 V, so they run on the usual single phase supply; at 10, 12 and 16 kW there are also 380 V versions. If you already have three phase, use it: the current on each phase drops and start-up is gentler. The details and the power thresholds, in single phase or three phase heat pump.